Begin with the server trays.
List the trays that will be connected, their required coolant flow and their permitted inlet conditions. Keep the equipment manufacturer's requirements with the rack configuration. Do not treat the rack heat load as a substitute for those requirements.
Each tray is a branch between the supply and return headers. A change to the tray count, hose arrangement or coupling can change the hydraulic behaviour of the rack.
Define the hydraulic boundary.
Establish what the cooling supply can provide at the rack and what the complete connected flow path requires. Include the manifold, hoses, connectors, cold plates and other relevant restrictions.
Parallel branches do not necessarily receive equal flow. Their resistance and the pressure distribution along the headers matter. Ask for the agreed method of evaluating branch distribution across the intended operating range.
Tray flow requirements, available pressure, component pressure losses, coolant properties and the installed configuration.
Check the physical connection.
Confirm the rack envelope, mounting points, supply and return orientation, port spacing and connector access. Review the space needed to connect, disconnect and service the equipment using the approved procedure.
Specify mating coupling parts and the hose assembly rather than relying on a connector family name alone. Check hose routing and permitted bend radius against tray travel, rack doors and cable paths.
Specify the fluid and the feedback loop.
Record the fluid product, glycol type, concentration and concentration basis. Choose property data for the operating temperature range. Define measured rack flow and paired supply and return temperature points if a thermal estimate is required.
For automated flow control, agree the flow setpoint source, actuator command and position feedback, minimum permitted flow, response limits, override and fault behaviour. Verify the selected flow sensor and any fluid correction against its calibration. Automatic concentration detection and individual branch balancing require separate specifications.
Use a rack-flow target to evaluate the total response, then check the trays against their own cooling requirements. A rack total cannot prove that each cold plate receives adequate flow.
Match the coolant and the materials.
Record the coolant chemistry and concentration, together with the wetted materials and seal materials throughout the connected circuit. Confirm operating pressure and temperature limits for the whole assembly.
Include cleanliness, filling, venting and shipping requirements in the agreed procedure. Compatibility with one fluid or one component does not establish compatibility for the complete loop.
Specify the information the team needs.
For each measurement, record the type, location, range, units and required accuracy. Identify whether a pressure value is a single-point measurement or a differential between defined points.
For valve control, agree the command interface, any position feedback and the required behaviour when power or communication is lost. Distinguish the requested position from measured flow.
Keep readings, relevant settings, timestamps and the connected tray configuration together. That makes later comparisons much more useful.
Agree the acceptance evidence.
Set the required tests and acceptance criteria before installation. The evidence should match the supplied assembly and the intended rack configuration.
- Approved mechanical and hydraulic drawings.
- Component, coolant and material compatibility information.
- Agreed cleanliness, leak and pressure-test evidence.
- Sensor checks and verification of valve commands and feedback.
- Operating readings recorded with the installed configuration.
- Service instructions, operating limits and change records.
Use the equipment manufacturer's requirements and the site's approved procedures to set the actual test methods and limits. This guide does not supply a universal pressure, temperature or flow rating.
Technical references
The following references provide general context for manifold and rack-loop design. They do not establish a FluidSensing certification or product rating.
Open Compute Project: Open Rack V3 Blind Mate Manifold Specification Lawrence Berkeley National Laboratory: Liquid-Cooled Rack Specification